What does a fiberglass cable tray load table show?
Each row is one tray series, defined by its side rail height and loading depth. Each column is a support span. The main cell is the safe uniform load: the weight of cable per foot or per metre that the tray may carry at that span, already divided by the safety factor printed on the table. Most tables add the deflection at that load and a K factor for working out deflection at lighter loads. North American tables name the NEMA class the series meets; British and Gulf tables usually give the IEC 61537 safe working load at each span instead, and some print both.
Read the footnotes before the numbers. Enduro states that its load-versus-span values come from the deflection measured at the mid-point of a single span, and that continuous spans may give higher ratings. Marshall-Tufflex measures its deflections with the joint between two ladders placed L/5 from a support and warns that deflection rises by about 30 percent at full load if that position is not kept. A table describes the installation it was tested in.
Reading two published tables
The Thomas & Betts (ABB) nonmetallic tray catalogue gives full straight-section tables at a 1.5 safety factor. Two of its series show how the numbers move.
| Support span | 8 ft (2.4 m) | 10 ft (3 m) | 12 ft (3.7 m) |
|---|---|---|---|
| Safe load, lb/ft | 205 | 144 | 100 |
| Safe load, kg/m | 303 | 214 | 148 |
| Deflection at that load | 1.18 in (30 mm) | 2.03 in (52 mm) | 2.92 in (74 mm) |
| K factor, in per lb/ft | 0.005 | 0.014 | 0.029 |
| Support span | 14 ft (4.3 m) | 16 ft (4.9 m) | 18 ft (5.5 m) | 20 ft (6.1 m) |
|---|---|---|---|---|
| Safe load, lb/ft | 272 | 208 | 164 | 133 |
| Safe load, kg/m | 405 | 310 | 244 | 198 |
| Deflection at that load | 3.64 in (92 mm) | 4.76 in (121 mm) | 6.01 in (153 mm) | 7.45 in (189 mm) |
| K factor, in per lb/ft | 0.0129 | 0.022 | 0.0352 | 0.0536 |
Values as printed in the Thomas & Betts (ABB) catalogue for its own tray. They show how to read a table and do not describe tray made from pultrx profiles.
The tables show three things. First, the safe load falls roughly with the square of the span: for Series 4, load × span² is about 13,100 at 8 ft and 14,400 at 10 and 12 ft (lb·ft). Doubling a span leaves about a quarter of the load. Second, the class is set by the longest span at which the series still carries the class load, so 12C and 20C describe where 100 lb/ft is reached, not how strong the tray is at short spans. Third, the deflection at full rated load is large: 74 mm on a 3.7 m span is about span/49, and 189 mm on 6.1 m is about span/32. A safe load with a 1.5 safety factor still allows a large sag.
Why deflection often decides the span
Glass fiber composites are far less stiff than steel, so a fiberglass tray reaches a visible sag well before it reaches its safe load. Some projects accept that; others write a deflection limit into the specification, for appearance, for cable bend radius at supports, or to keep covers seated. When a limit applies, work it out with the K factor: deflection = load × K. At 10 ft, Series 4 has K = 0.014 in per lb/ft, so 70 lb/ft gives 0.98 in (25 mm). The catalogue allows this for loads lighter than the tabulated one.
Turned around, the K factor gives the load a deflection limit allows: allowed load = limit ÷ K. With a limit of span/100 at 10 ft (1.2 in), Series 4 may carry 1.2 ÷ 0.014 = 86 lb/ft, well below the 144 lb/ft safe load. Span/100 is an example chosen here; use the limit in your project specification. Thomas & Betts (ABB) adds that a tray running continuously over several supports deflects by as much as 50 percent less than the single span its table assumes.
| Span | Published safe load | Span/100 limit | Load allowed by the limit (limit ÷ K) | Which governs |
|---|---|---|---|---|
| 8 ft (2.4 m) | 205 lb/ft | 0.96 in (24 mm) | 192 lb/ft | Deflection, narrowly |
| 10 ft (3 m) | 144 lb/ft | 1.2 in (30 mm) | 86 lb/ft | Deflection |
| 12 ft (3.7 m) | 100 lb/ft | 1.44 in (37 mm) | 50 lb/ft | Deflection |
The catalogue rounds its K factors. At 8 ft the printed deflection, 1.18 in at 205 lb/ft, implies about 0.0058 rather than 0.005; with that value the 8 ft limit allows about 167 lb/ft, and the 8 ft case in the worked example below sags about 8.9 mm instead of 7.7 mm. The conclusions do not change, but where the margin is small, work from the printed deflection.
Safety factors: NEMA classes and IEC 61537 are not the same number
Before comparing two tables, check the factor each one has divided by. The Enduro specification defines NEMA working-load classes on a 1.5 safety factor, and the Thomas & Betts (ABB) tables above use 1.5. Enduro publishes some of its own series, marked with a plus sign, on a 2.0 factor and says to multiply those loads by 1.33 to compare them with the 1.5 basis. Marshall-Tufflex states a safety coefficient above 1.7 for its IEC 61537 data. A kg/m figure from an IEC table and a lb/ft figure from a NEMA table can therefore describe different margins even after unit conversion. Note also which standard a table cites: Thomas & Betts (ABB) prints its class table under NEMA VE 1 and CSA C22.2 No. 126.1, while NEMA FG 1 is the fiberglass cable tray standard that MITA cites beside IEC 61537.
| Source | How load is stated | Safety basis printed |
|---|---|---|
| NEMA-class tables (Enduro, Thomas & Betts) | lb/ft and kg/m at spans in feet; class such as 12C or 20C | 1.5 |
| Enduro '+' classes | lb/ft at spans in feet | 2.0; multiply by 1.33 to compare on 1.5 |
| Marshall-Tufflex, IEC 61537 | kg/m or kN/m at spans in metres | Safety coefficient above 1.7 |
| MITA (Wibe Group), BS EN IEC 61537 | kg/m at 1.5, 2, 2.5, 3, 4, 5 and 6 m, beside NEMA class columns | No factor printed; SWL given to BS EN IEC 61537 and NEMA FG 1 |
Units: lb/ft, kg/m and kN/m
| From | To | Multiply by | Example |
|---|---|---|---|
| lb/ft | kg/m | 1.488 | 100 lb/ft = 149 kg/m |
| kg/m | kN/m | 0.00981 | 149 kg/m = 1.46 kN/m |
| lb/ft | kN/m | 0.0146 | 50 lb/ft = 0.73 kN/m |
| ft | m | 0.3048 | 20 ft = 6.1 m; 12 ft = 3.7 m |
| in | mm | 25.4 | 2.92 in = 74 mm |
Worked example: sizing one tray run
The inputs here are invented to show the method. An outdoor run on a pipe rack carries eight power cables at 6.5 kg/m each, with supports every 3 m (10 ft). A 30 kg junction box is fixed at mid-span. The tray is isophthalic polyester and the hottest expected service temperature, sun included, is 52 °C (125 °F). The project limits deflection to span/200.
- 01
Cable load
8 × 6.5 kg/m = 52 kg/m. Add 25 percent for future cables: 13 kg/m. Running total 65 kg/m.
- 02
Point load
Equivalent uniform load = 2P ÷ L = 2 × 30 kg ÷ 3 m = 20 kg/m. Design load 85 kg/m (57 lb/ft).
- 03
Temperature
Isophthalic polyester keeps about 78 percent of its strength at 125 °F (52 °C) in continuous service, in the Thomas & Betts (ABB) derating table. Needed safe load at room temperature: 85 ÷ 0.78 = 109 kg/m.
- 04
Strength check
Series 4 lists 214 kg/m at 10 ft (3 m). 214 is more than 109, so strength passes with margin.
- 05
Deflection check
57 lb/ft × K 0.014 = 0.80 in, about 20 mm, or span/150. The limit is span/200, 15 mm at 3 m. Deflection fails.
- 06
Fix
Move supports to 8 ft (2.44 m). Point load becomes 2 × 30 ÷ 2.44 = 25 kg/m, design load 90 kg/m (60.5 lb/ft), deflection 60.5 × 0.005 = 0.30 in (7.7 mm). The limit at 2.44 m is 12.2 mm. Passes. The other route is a deeper side rail at the original span.
Point loads, fittings and end spans
- Point loads: a junction box, a branch tray or a valve actuator bracket fixed to the tray is converted with 2P ÷ L and added before choosing a class. The tables assume uniformly spread cable.
- Fittings: the Enduro specification requires fittings designed to carry the same load as straight sections. Thomas & Betts (ABB) refers support of fittings to NEMA VE 2. Marshall-Tufflex asks for an extra central support under any fitting with a bend radius over 250 mm or a width over 400 mm.
- Joints: keep splices near a support. The Marshall-Tufflex figures assume the joint L/5 from the support; further out, its deflections rise by about 30 percent.
- Hot runs: derate the safe load for the hottest service temperature before reading the table, as in the worked example. The K factors are room-temperature values, so a hot run also sags somewhat more than the deflection check shows; leave margin.
What to ask a tray supplier for
| Ask | Why |
|---|---|
| Safe load at your span, in your units | Interpolating across a table that skips your span can mislead; load falls with the square of the span |
| Safety factor behind the table | 1.5, 1.7 and 2.0 are all in use |
| Deflection at that load, or the K factor | A safe-load figure does not cap sag |
| Single or continuous span basis, and joint position | Both change deflection by tens of percent |
| Resin and temperature derating | Polyester and vinyl ester lose strength at different rates |
| Which tray series and rung spacing the table covers | The table applies only to the series tested |
What does pultrx supply for cable tray?
pultrx quotes pultruded side rails, rungs, troughs and cover sheet to the tray maker's drawing, from the Henan Zhongsheng factory. A load table belongs to a tested tray system, so it comes from the tray designer or the system maker. For the profiles, ask for the section dimensions and material data your tray designer needs, and name any load class or IEC 61537 test the finished tray must meet on the RFQ.
Published figures are examples, not pultrx ratings
Sources and further reading
- Thomas & Betts (ABB): Nonmetallic cable tray systems catalogue and technical information
Series 4 and Series H6C straight-section tables (safe load, deflection and K factor at a 1.5 safety factor), the span and load class table cited to NEMA VE 1 and CSA C22.2 No. 126.1, the 2P ÷ L conversion, and the note that continuous spans reduce deflection by as much as 50 percent.
- Enduro (Creative Composites Group): Ladder type cable tray specification and data
NEMA working-load classes on a 1.5 safety factor, '+' classes published on a 2.0 safety factor with a 1.33 conversion, single-span test basis, and fittings designed for the same load as straight sections.
- Marshall-Tufflex: GRP ladder and tray brochure
IEC 61537 load data with a safety coefficient above 1.7; deflection measured with the joint L/5 from a support, about 30 percent more deflection otherwise; extra support for large bends and wide fittings.
- MITA (Wibe Group) GRP cable ladders, trays and trough technical guide
BS EN IEC 61537 safe working loads at spans of 1.5 to 6 m printed beside NEMA class columns for each tray.
Questions buyers ask
How much weight can a fiberglass cable tray hold?
It depends on the side rail and the support span. One published 4 in rail series carries 205 lb/ft (303 kg/m) at 8 ft but 100 lb/ft (148 kg/m) at 12 ft; a 6 in rail series carries 133 lb/ft (198 kg/m) at 20 ft. Read the maker's table at your span and check deflection too.
What is the maximum span for fiberglass cable tray?
The common class table stops at 20 ft (6.1 m), and published IEC 61537 tables run to about 6 m. Longer spans exist: Enduro lists a 30C+ series on a 10 in rail. Long spans need deep side rails; the 20C series in this guide uses a 6 in rail. Deflection usually sets the practical span before strength does.
Why does fiberglass cable tray deflect more than steel tray?
Glass fiber composite is much less stiff than steel. At full rated load, the published 4 in series sags 74 mm on a 3.7 m span, about span/49. Where the project limits deflection, the allowed load is the limit divided by the K factor.
Can I convert a NEMA class into an IEC 61537 safe working load?
The units convert (100 lb/ft = 149 kg/m = 1.46 kN/m), but the safety factors differ: 1.5 in NEMA-class tables, above 1.7 in at least one maker's IEC 61537 data. Ask the maker for the value on the basis your project uses; some print both.
Does a continuous run carry more than a single span?
It deflects less. Thomas & Betts (ABB) says continuous spans reduce deflection by as much as 50 percent, and Enduro says continuous spans may give higher load ratings than its single-span tables.
How is a point load added to a cable tray load?
Convert it to an equivalent uniform load, 2P ÷ L, where P is the point load and L the support span. A 30 kg box on a 3 m span adds 20 kg/m.
Summary
How do you read a fiberglass cable tray load table?
Find the support span in the column headings and read the safe load for the tray series in lb/ft or kg/m. Check that it covers the cable weight plus future fill and any point load (2P ÷ L), divided by the temperature derating factor. Then check deflection: multiply the actual load by the K factor for that span and compare it with the project limit.
- Safe load
- Uniform load per length at a stated support span, single span, with a stated safety factor (1.5 in NEMA-class tables)
- Example, 12C
- One published 4 in rail series: 205, 144 and 100 lb/ft at 8, 10 and 12 ft (303, 214 and 148 kg/m)
- Example, 20C
- One published 6 in rail series: 272, 208, 164 and 133 lb/ft at 14, 16, 18 and 20 ft
- Deflection
- Load × K factor; at full rated load the 4 in series sags 2.92 in (74 mm) at 12 ft
- Point load
- Equivalent uniform load = 2P ÷ L
- IEC 61537
- Safe working load in kg/m or kN/m per span; one British maker states a safety coefficient above 1.7